Transformer inrush current: causes, size and protection

110 kV to 35 kV oil-immersed step-down power transformer with ONAN/ONAF radiators and cooling fans in an outdoor substation product scene

Inrush current is the large, short-lived current a transformer draws when it is first energised. It happens because the core is driven into magnetic saturation for the first few cycles, so the magnetising current, normally a fraction of a percent of rated current, can briefly reach several times rated current. Typical first-peak values are in the range of about 5 to 15 times rated current, decaying over tenths of a second to several seconds. Protection must be set to ride through it without missing real faults.

Key takeaways

  • Magnetising inrush is caused by core saturation at switch-on, not by a fault, and it flows only in the energised winding.
  • Its size depends on the switching point on the voltage wave, residual flux in the core, source impedance and core design.
  • Inrush current is rich in second harmonic, which differential relays use to tell it apart from an internal fault.
  • Fuses, overcurrent relays and breaker trip units must sit above the inrush point, commonly approximated as 8 to 12 times rated current for 0.1 s.
  • Controlled switching, pre-insertion resistors and sequential energisation reduce inrush where voltage dips or nuisance trips are a problem.

What causes transformer inrush current?

In steady state, the flux in a transformer core lags the applied voltage by 90 degrees and swings symmetrically between a positive and negative peak just below the saturation level of the core steel. The magnetising current needed for that flux is small.

When the transformer is switched on, the flux must start from whatever value was left in the core (the residual flux) rather than from the steady-state value matching the instant of switching. The flux then contains a DC offset. In the worst case, switching at a voltage zero with residual flux of the same polarity, the flux can try to reach more than twice its normal peak plus the residual value. The core steel cannot support that without saturating, and once it saturates the winding behaves almost like an air-cored coil with very low inductance. The current rises steeply until the voltage reverses.

Three factors dominate:

  1. Switching angle. Energising at a voltage peak gives the least offset; at a voltage zero, the most.
  2. Residual flux. Left in the core when the transformer was last switched off, it can add to or subtract from the offset.
  3. Saturation margin. Modern designs run the core at higher flux density for lower cost and losses, which leaves less margin before saturation and can increase inrush.

Source impedance and the winding resistance limit the peak and determine the decay. A strong source (low impedance) gives a higher peak. In a three-phase transformer the three phases are switched at different points on the wave, so at least one phase normally sees significant offset.

How large is transformer inrush current, and how long does it last?

Inrush is quoted as a multiple of rated current. Published figures vary widely, so the values below are cautious typical ranges, not guarantees.

ItemTypical rangeNotes
First peak, distribution transformersAbout 8 to 15 × rated currentSmaller units often show higher multiples
First peak, large power transformersAbout 5 to 10 × rated currentHigher source impedance relative to rating
Decay timeTenths of a second (small units) to several seconds or more (large units)Time constant depends on winding resistance and source X/R
Second harmonic contentOften well above 15 to 20 % of fundamentalFalls as inrush decays; can be lower with modern core steels
Protection screening point8 to 12 × rated current at 0.1 sCommonly used in coordination studies; confirm with supplier data

Inrush is asymmetric: it appears as unidirectional peaks with gaps in between, which makes it look very different from a symmetrical fault current. It also depends on which side you energise. Energising from the inner winding (usually LV) tends to give higher inrush than energising from the outer HV winding, because the inner winding has lower air-core inductance. If your design will be back-fed, as in a solar or BESS step-up transformer energised from the grid side, ask the manufacturer for inrush data on the energised winding.

Dry-type cast-resin transformers can show inrush at the upper end of the ranges above. If you need numbers for a study, ask the manufacturer for calculated or measured inrush for your specific design and source.

How does magnetising inrush affect protection settings?

Fuses. HV fuses protecting distribution transformers must withstand inrush without melting or ageing. Fuse selection tables in fuse standards and supplier catalogues already account for this, which is why a fuse rated about 1.5 to 2 times transformer current is common. The fuse's minimum melting curve should sit to the right of the inrush point (for example 12 × rated current at 0.1 s), and to the left of the transformer's thermal withstand curve.

Overcurrent relays. The instantaneous element (ANSI 50) must be set above the peak inrush seen by the relay, or delayed slightly. The time-overcurrent element (51) curve must pass above the inrush point. Setting the instantaneous element above the maximum LV through-fault current referred to the HV side is a common approach, which also clears inrush.

Differential relays. Inrush flows only into the energised winding, so a transformer differential relay (87T) sees it as a difference current, exactly like an internal fault. Relays block or restrain operation when the second harmonic content of the differential current exceeds a set percentage, typically around 15 to 20 percent. Many relays also use waveform-based methods because modern low-loss cores can produce inrush with lower second harmonic. An unrestrained high-set differential element trips for heavy internal faults regardless of harmonics.

LV breakers. Electronic trip units on breakers feeding a transformer from the LV side, for example a back-fed BESS or generator step-up unit, need their instantaneous pickup set above the inrush peak.

Earth-fault elements. Unbalanced inrush between phases can produce residual current, so short time delays on sensitive earth-fault elements may be needed.

What is sympathetic inrush?

When a transformer is energised next to one already in service, the inrush of the incoming unit causes a DC voltage drop across the shared source resistance. That can drive the in-service transformer into partial saturation, so it too draws an asymmetric current of opposite polarity. The combined current can last much longer than ordinary inrush and can trip relays on the healthy transformer. It is a particular issue in solar and wind collector systems, where many step-up transformers on one feeder are energised in sequence, and in prefabricated substations with two transformers on a common bus.

How can inrush surge current be reduced?

  1. Controlled (point-on-wave) switching. A controller closes each pole of the breaker at the optimum instant, ideally taking residual flux into account. This can reduce inrush dramatically on large transformers.
  2. Pre-insertion resistors. A resistor is inserted for a short time when the breaker closes, damping the inrush, then bypassed.
  3. Sequential energisation. On collector networks, energise transformers in groups or one at a time to avoid a large combined inrush and sympathetic effects.
  4. Residual flux control. Demagnetising after DC winding resistance tests reduces residual flux. This is good practice after site testing.
  5. Energise from the outer winding where the system allows, typically the HV side.
  6. Design choice. A lower operating flux density gives more saturation margin, at some cost in material.

For most distribution transformers, none of this is necessary. Correctly selected fuses or relays ride through inrush with no special measures.

Can inrush current damage a transformer?

Occasional energisation is part of normal service and transformers are designed for it. The current is lower than a through fault, but it is asymmetric and can last longer, producing mechanical forces in the windings. Very frequent energisation, for example in some renewable or storage plants switched daily, increases cumulative stress. If your duty involves frequent switching, include it in the specification so the designer can account for it. Our transformer RFQ checklist covers the duty data to include.

Inrush also causes temporary voltage dips and harmonics on the network. For weak grids or island systems, check the dip with a study before choosing the transformer size and energisation scheme.

Inrush considerations by application

  • Utility substations. A 110 kV to 35 kV step-down power transformer will typically be protected by a differential relay with harmonic restraint and an overcurrent backup coordinated for inrush.
  • Distribution networks. For an 11 kV to 400 V distribution transformer, HV fuses or a ring main unit with fuse-switch combinations are selected from tables that already allow for inrush. See ring main units: SF6 vs solid-insulated.
  • Renewables and storage. Collector-system transformers in PV step-up substations are often energised in sequence and should be checked for sympathetic inrush.
  • Generators and islanded systems. A diesel generator energising a large transformer may see a severe voltage dip. Soft energisation or staged switching is sometimes needed.

Correct kVA sizing also matters: an oversized transformer has higher inrush relative to the actual load. See kVA vs kW explained.

Frequently asked questions

Why does a transformer trip when energised but not afterwards?

Usually because a relay or trip unit is set below the inrush current or without harmonic restraint. Check the instantaneous overcurrent setting and the differential relay's second harmonic blocking before suspecting an internal fault.

Is inrush current the same as short-circuit current?

No. Inrush is a magnetising phenomenon in a healthy transformer, flows only in the energised winding and contains large even harmonics. Short-circuit current is driven by a fault and is limited mainly by impedance.

Does a dry-type transformer have higher inrush than an oil-immersed one?

It can, depending on core design and flux density. Cast-resin units are sometimes quoted at the higher end of the typical range. Ask the supplier for design-specific values if the study is sensitive.

Does inrush happen when a transformer is re-energised quickly?

Yes, and residual flux after a recent de-energisation can make the next inrush worse if it adds to the offset. That is why some large transformers use controlled switching that measures residual flux.

What protection settings are used for magnetising inrush?

Common practice is second harmonic blocking of 15 to 20 percent on differential relays, instantaneous overcurrent above the inrush peak, and time-overcurrent curves above a screening point of about 8 to 12 times rated current at 0.1 s. Settings must be confirmed by a coordination study.

Ask for inrush data with your proposal

If you are planning protection settings or an energisation sequence, send us your single-line diagram, source fault level and switching arrangement. We will include the relevant transformer data in our technical proposal. Contact Toppower Asia.

Toppower Asia Engineering Team

Application and sales engineers at Shanghai Toppower-Asia Co., Ltd. who review specifications and prepare technical proposals for transformers, switchgear, substations and battery storage. Questions about this article: kevin@toppower-asia.com.

More on transformers

Send your single-line diagram. Get a technical proposal back.

Tell us the rating, voltages and site. Our engineers review it against your network before pricing, and reply with ratings, losses, dimensions, test scope and a quotation.

Rated power, voltages, frequency, standard, site conditions and destination port help us reply with a firm proposal.

Send via WhatsApp

Replies come from kevin@toppower-asia.com. Office hours are Monday to Friday, 9:00–18:00 China Standard Time.

Press Enter to see all matching products. Use ↑ ↓ to move through results.