# What is considered high voltage? LV, MV and HV classes explained

Published 2026-10-13 by Toppower Asia Engineering Team · https://www.toppower-asia.com/blog/voltage-levels-lv-mv-hv-explained/

What is considered high voltage depends on the standard. In IEC practice, low voltage is up to 1,000 V AC (1,500 V DC) and anything above 1 kV is formally high voltage, with "medium voltage" used informally for distribution levels up to about 35 kV to 52 kV. ANSI C84.1 instead defines medium voltage as above 1 kV and below 100 kV, and high voltage as 100 kV to 230 kV.

## Key takeaways

- Low voltage is up to 1,000 V AC in both IEC and ANSI practice; IEC 60038 and the EU Low Voltage Directive also cover DC up to 1,500 V.
- IEC does not fix a precise medium voltage range. The IEC vocabulary says the boundary between medium and high voltage depends on local practice, and it often lies somewhere between 30 kV and 100 kV.
- ANSI C84.1 uses fixed classes: medium voltage above 1 kV and below 100 kV, high voltage 100 kV to 230 kV, extra high voltage above 230 kV and below 1,000 kV, and ultra high voltage from 1,000 kV.
- In equipment standards, IEC 62271 covers switchgear above 1 kV, so an "HV" switchgear catalogue in IEC markets often includes 12 kV and 24 kV panels.
- Always state the nominal system voltage and the rated (highest) equipment voltage in specifications rather than relying on the class name.

## What is low voltage?

Low voltage (LV) is the range used for final distribution and most end-use equipment. IEC 60038 lists standard LV systems up to 1,000 V AC, such as 230/400 V and 400/690 V at 50 Hz, and 120/208 V, 277/480 V and 347/600 V at 60 Hz. The EU Low Voltage Directive (2014/35/EU) applies to equipment between 50 V and 1,000 V AC and between 75 V and 1,500 V DC. ANSI C84.1 also places the LV boundary at 1,000 V.

Below LV sits extra-low voltage (ELV), generally up to 50 V AC or 120 V ripple-free DC, used where electric shock risk must be minimised.

LV equipment includes switchboards, panelboards, motor control centres and air circuit breakers. Our article on [switchgear vs switchboard vs panelboard](https://www.toppower-asia.com/blog/switchgear-vs-switchboard-vs-panelboard/) explains how LV assemblies are classified.

Solar plants are a special case: modern PV arrays commonly run at up to 1,500 V DC, which is still LV by the IEC and EU definitions, but the inverter AC output (often 480 V to 800 V) is then stepped up to medium voltage.

## What is the medium voltage range?

Medium voltage (MV) is where most distribution networks operate. Common nominal system voltages include 3.3 kV, 6.6 kV, 11 kV, 13.8 kV, 20 kV, 22 kV, 33 kV and 34.5 kV.

The definition differs by standard:

- **IEC.** The International Electrotechnical Vocabulary (IEV 601-01-28) defines medium voltage only as voltage levels lying between low and high voltage, and notes that the boundary with high voltage depends on local circumstances and history. IEC 60038 itself groups three-phase systems into tables for above 1 kV up to 35 kV, 35 kV to 230 kV, and above 230 kV, without naming them MV or HV. In switchgear, IEC 62271-200 covers metal-enclosed switchgear above 1 kV up to and including 52 kV, which many people treat as the practical MV ceiling.
- **ANSI.** ANSI C84.1 defines medium voltage as greater than 1,000 V and less than 100 kV. That makes 69 kV a medium voltage in ANSI terms, though many US utilities call it sub-transmission.
- **UK and some other markets.** The term medium voltage is not traditionally used; anything above 1 kV is often simply called high voltage.

Our [medium voltage switchgear guide](https://www.toppower-asia.com/blog/medium-voltage-switchgear-guide/) covers the equipment used in this range.

## What is considered high voltage?

The high voltage definition is where IEC and ANSI usage diverges most:

- In IEC terminology and in many safety regulations, high voltage means any voltage above 1 kV AC (1.5 kV DC). That is why a 12 kV metal-clad panel is called "HV switchgear" in IEC markets, as in our [indoor HV metal-clad switchgear for 12 kV to 35 kV](https://www.toppower-asia.com/products/switchgear/indoor-hv-metal-clad-switchgear-12kv-24kv-35kv-4000a/).
- In network planning, utilities usually reserve "high voltage" for transmission and sub-transmission levels, such as 66 kV, 110 kV, 132 kV, 220 kV and above.
- ANSI C84.1 defines high voltage as from 100 kV up to and including 230 kV.

So a 33 kV cable may be "high voltage" for a safety-rules permit, "medium voltage" in a distribution design report and "MV" in an ANSI-based specification. Both are correct in context.

## What is extra high voltage?

Extra high voltage (EHV) is used for bulk transmission over long distances. In ANSI C84.1 it covers voltages above 230 kV and below 1,000 kV, which includes common system voltages such as 345 kV, 500 kV and 765 kV. Ultra high voltage (UHV) starts at 1,000 kV in ANSI terms.

IEC does not define EHV as a fixed range, but IEC 60038 tabulates systems above 230 kV separately, and IEC 62271-1 splits switchgear rated voltages into range I (up to and including 245 kV) and range II (above 245 kV), with different insulation test requirements. In practice, many utilities in IEC markets call 220 kV and above EHV.

Transformers at these levels are large, engineered units, such as our [EHV 220 kV/230 kV power transformer](https://www.toppower-asia.com/products/power-transformer/ehv-220kv-230kv-power-transformer-31500-to-420000-kva/).

## How do IEC and ANSI voltage classes compare?

| Class | IEC usage | ANSI C84.1 | Typical system voltages |
| --- | --- | --- | --- |
| Extra-low voltage | Up to 50 V AC / 120 V ripple-free DC | Not a C84.1 class | 12 V, 24 V, 48 V |
| Low voltage (LV) | Up to 1,000 V AC / 1,500 V DC | 1,000 V or less | 230/400 V, 277/480 V, 400/690 V |
| Medium voltage (MV) | Between LV and HV; boundary set by local practice, often taken as up to 35 kV or 52 kV | Above 1 kV and below 100 kV | 6.6 kV, 11 kV, 13.8 kV, 22 kV, 33 kV, 34.5 kV |
| High voltage (HV) | Formally above 1 kV; in network practice, transmission levels | 100 kV to 230 kV | 66 kV, 110 kV, 132 kV, 220 kV |
| Extra high voltage (EHV) | Not formally defined; often 220 kV and above | Above 230 kV and below 1,000 kV | 330 kV, 400 kV, 500 kV, 765 kV |
| Ultra high voltage (UHV) | Not formally defined | 1,000 kV and above | 1,000 kV AC, higher DC links |

## What is the difference between nominal voltage and rated voltage?

Specifications often mix these terms, which leads to errors:

- **Nominal system voltage** is the name of the network, for example 11 kV or 33 kV.
- **Highest voltage for equipment**, or **rated voltage** in IEC 62271, is the maximum system voltage the equipment is designed for, for example 12 kV for an 11 kV network, 24 kV for 20 kV or 22 kV, and 36 kV or 40.5 kV for 33 kV or 35 kV.

Typical pairings are shown below.

| Nominal system voltage | Typical IEC rated voltage of switchgear | Typical ANSI/IEEE maximum voltage |
| --- | --- | --- |
| 6.6 kV | 7.2 kV | 8.25 kV class (4.76 kV class for 4.16 kV systems) |
| 10 kV / 11 kV | 12 kV | 15 kV class for 12.47 kV / 13.8 kV systems |
| 20 kV / 22 kV | 24 kV | 27 kV class for 23 kV / 24.9 kV systems |
| 33 kV / 35 kV | 36 kV or 40.5 kV | 38 kV class for 34.5 kV systems |

For transformers, the windings carry their own rated voltages and insulation levels under IEC 60076 or IEEE C57; our article on [IEC 60076 vs IEEE C57 transformer standards](https://www.toppower-asia.com/blog/iec-60076-vs-ieee-c57-transformer-standards/) explains the differences.

## Why does the voltage class matter for buyers?

1. **Standards and tests.** The class determines which product standard applies and the insulation test levels (power-frequency and lightning impulse withstand).
2. **Clearances and enclosure design.** Higher voltage needs greater distances in air or a better insulating medium.
3. **Safety rules.** Work permits, training and PPE requirements change when the voltage exceeds 1 kV.
4. **Current and cable size.** For the same power, higher voltage means lower current. You can check full-load currents at different voltages with our [transformer calculator](https://www.toppower-asia.com/tools/transformer-calculator/).
5. **Network role.** The class tells you where the equipment sits in the system, from transmission to final distribution, as described in [what is a substation](https://www.toppower-asia.com/blog/what-is-a-substation/).

## Frequently asked questions

### Is 11 kV high voltage or medium voltage?

Both, depending on context. By the IEC formal definition and in many safety rules, 11 kV is high voltage because it exceeds 1 kV. In distribution practice and under ANSI C84.1, it is medium voltage. Specify the nominal and rated voltage to avoid ambiguity.

### What is low voltage in a building?

In most buildings, LV means the 230/400 V or 120/208 V and 277/480 V distribution supplying lighting, sockets, HVAC and motors, up to 1,000 V AC. Below 50 V AC, circuits such as controls and some lighting are extra-low voltage.

### What is the medium voltage range in the US?

ANSI C84.1 defines medium voltage as above 1,000 V and below 100 kV. Common US distribution voltages in this range include 4.16 kV, 12.47 kV, 13.2 kV, 13.8 kV, 24.9 kV and 34.5 kV.

### What is the high voltage definition in IEC standards?

IEC uses high voltage formally for anything above 1 kV AC or 1.5 kV DC, which is why IEC 62271 is titled for high-voltage switchgear even though it covers 12 kV equipment. The IEC vocabulary treats medium voltage as an intermediate band whose upper limit depends on local practice.

### Is 1,500 V DC solar considered low voltage?

Yes, under IEC 60038 and the EU Low Voltage Directive, which cover DC up to 1,500 V. National installation rules may still impose specific requirements for DC systems at this level.

## Specify voltages with confidence

Send us your single-line diagram with nominal system voltages, fault levels and the standards your project follows. Our engineers will confirm the correct rated voltages and insulation levels in a technical proposal. [Contact our engineering team](https://www.toppower-asia.com/contact/).