# Medium voltage switchgear: metal-clad, metal-enclosed and RMUs

Published 2026-10-13 by Toppower Asia Engineering Team · https://www.toppower-asia.com/blog/medium-voltage-switchgear-guide/

Medium voltage switchgear controls and protects circuits from above 1 kV up to about 52 kV, typically at 12 kV, 24 kV and 36 kV ratings for 10–11 kV, 20–22 kV and 33 kV networks. The main families are air-insulated metal-clad panels with withdrawable vacuum breakers, compact gas- or solid-insulated metal-enclosed panels, and ring main units for secondary distribution.

## Key takeaways

- Under IEC, MV switchgear is "metal-enclosed" switchgear to IEC 62271-200. "Metal-clad" remains a widely used trade term and is formally defined in North America by IEEE C37.20.2.
- Air-insulated withdrawable switchgear (for example KYN28) suits primary substations and industrial main switch rooms where maintainability matters.
- Gas- and solid-insulated switchgear is smaller and less sensitive to pollution and humidity, which helps in compact substations, offshore and dusty sites.
- Ring main units are compact switchgear for cable rings and transformer tee-offs.
- Specify by ratings, LSC category, partition class, IAC and installation conditions, not by product name.

## What is medium voltage switchgear?

Medium voltage switchgear is the assembly of circuit breakers, switches, disconnectors, earthing switches, instrument transformers, relays and busbars that distributes power at MV. It sits at the heart of primary and secondary substations, industrial plants, solar and wind collection systems, data centres and battery storage sites.

The IEC standard for this equipment is [IEC 62271-200](https://webstore.iec.ch/en/publication/63466), which covers AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV. The switching devices inside have their own parts of the IEC 62271 series, such as IEC 62271-100 for circuit breakers.

Voltage class boundaries vary between standards and countries. Our article on [low, medium and high voltage classes](https://www.toppower-asia.com/blog/voltage-levels-lv-mv-hv-explained/) explains the common definitions.

## What are the standard MV switchgear voltage ratings?

The rated voltage of switchgear is the highest system voltage it is designed for, so it is always above the nominal network voltage.

| Nominal network voltage | IEC rated voltage | Typical IEC insulation level (power frequency / lightning impulse) | North American class (IEEE C37.20.2) |
|---|---|---|---|
| 6–6.6 kV | 7.2 kV | 20 kV / 60 kV | 8.25 kV |
| 10–11 kV | 12 kV | 28 kV / 75 kV | 15 kV |
| 13.8 kV | 17.5 kV (IEC) or 15 kV class | 38 kV / 95 kV | 15 kV |
| 20–22 kV | 24 kV | 50 kV / 125 kV | 27 kV |
| 33 kV | 36 kV | 70 kV / 170 kV | 38 kV |
| 35 kV (Chinese practice) | 40.5 kV | 95 kV / 185 kV | 38 kV |

Some national standards and utility specifications require higher insulation levels than the IEC values shown, so confirm the required values for your project. Typical rated busbar currents range from 630 A to 4,000 A, and short-time withstand currents from 16 kA to 40 kA or more.

## What is the difference between metal-clad and metal-enclosed switchgear?

This is the most common source of confusion in MV specifications, because the two standards systems use the words differently.

**In IEEE C37.20.2 (North America)**, metal-clad switchgear is a specific type of metal-enclosed switchgear with:

- a removable (draw-out) main switching device, typically a vacuum circuit breaker;
- major parts (breaker, busbars, cable connections, instruments) in separate earthed metal compartments;
- insulated main bus;
- automatic shutters that cover the primary contacts when the breaker is withdrawn;
- low-voltage instruments and relays separated from primary circuits by earthed metal barriers;
- mechanical interlocks for safe operation.

Other types, such as metal-enclosed interrupter switchgear to IEEE C37.20.3, use load-break switches and fuses rather than draw-out breakers.

**In IEC 62271-200**, all such equipment is metal-enclosed switchgear. The older IEC classes of metal-clad, compartmented and cubicle have been replaced by two characteristics:

| IEC characteristic | Options | What it means |
|---|---|---|
| Loss of service continuity (LSC) | LSC1, LSC2 (with LSC2A and LSC2B) | How much of the switchgear must be de-energised to open an accessible compartment. LSC2B allows a breaker compartment to be accessed while the busbar, adjacent panels and the cable compartment of that unit stay energised |
| Partition class | PM (metallic partitions and shutters), PI (insulating partitions or shutters) | What separates live parts from an opened compartment |

In practice, "metal-clad switchgear" on an IEC tender usually means withdrawable switchgear with LSC2B and partition class PM. Writing those characteristics into the specification removes ambiguity.

## Air-insulated vs gas-insulated MV switchgear: which suits your site?

The insulation medium shapes the footprint, environmental sensitivity and maintenance approach.

| Feature | Air-insulated switchgear (AIS) | Gas-insulated switchgear (GIS) | Solid-insulated switchgear (SIS) |
|---|---|---|---|
| Insulation of main circuits | Air, with insulators and sometimes insulated busbars | SF6 or an alternative gas in sealed tanks | Epoxy-encapsulated poles and busbars |
| Typical breaker | Withdrawable vacuum circuit breaker | Fixed vacuum or SF6 breaker inside the tank | Fixed vacuum breaker |
| Footprint | Largest, especially at 36 kV | Smallest | Compact, close to GIS at 12–24 kV |
| Sensitivity to humidity, dust, altitude | Higher; may need heaters, sealing, altitude correction | Very low for the main circuit | Low, if interfaces are well executed |
| Maintenance | Accessible breaker and contacts; easy replacement | Sealed for life; gas monitoring | No gas handling; inspect interfaces |
| Environmental profile | No F-gas | SF6 has a very high global warming potential; F-gas restrictions apply in some regions | No F-gas |

Air-insulated designs such as the [KYN28 metal-clad main switchboard for 10–33 kV](https://www.toppower-asia.com/products/switchgear/kyn28-metal-clad-main-switchboard-10kv-to-33kv-4000a/) remain the workhorse for primary substations and industrial main switch rooms. Gas-insulated cabinets such as our [SF6 gas-insulated MV switch cabinet for 12–33 kV](https://www.toppower-asia.com/products/switchgear/sf6-gas-insulated-medium-voltage-switch-cabinet-12kv/) suit compact or harsh sites. For a deeper comparison read [gas-insulated vs air-insulated switchgear](https://www.toppower-asia.com/blog/gas-insulated-vs-air-insulated-switchgear/), and for interrupting technology see [vacuum vs SF6 circuit breakers](https://www.toppower-asia.com/blog/vacuum-vs-sf6-circuit-breakers/).

## Where do ring main units fit?

A ring main unit (RMU) is compact, usually gas- or solid-insulated MV switchgear designed for secondary distribution. It typically has two load-break switches for the ring cables and one tee-off with a switch-fuse or vacuum circuit breaker to protect a distribution transformer. RMUs are found in compact substations, building switch rooms, wind turbines and solar inverter stations.

They are not a substitute for a main switchgear line-up at a primary substation, where you need many feeders, bus sections and full relay protection, but they are far more economical at each distribution point. Our article on [SF6, solid-insulated and air-insulated RMUs](https://www.toppower-asia.com/blog/ring-main-unit-sf6-vs-solid-insulated/) covers configurations such as CCV and CCF.

## How do you specify medium voltage switchgear?

A complete MV switchgear specification lets suppliers quote like for like. Include:

1. **Single-line diagram** with incomers, bus sections, bus couplers, feeders, metering and earthing transformer or neutral earthing arrangements.
2. **Network data:** nominal and rated voltage, frequency, system earthing method, prospective short-circuit current and duration.
3. **Ratings:** busbar and feeder rated currents, short-time withstand current and duration, peak withstand current, insulation level.
4. **Type and construction:** air-, gas- or solid-insulated; withdrawable or fixed; LSC category and partition class.
5. **Internal arc classification:** for example IAC AFLR 25 kA 1 s, matched to the room layout and arc venting. See [arc flash and internal arc classification](https://www.toppower-asia.com/blog/arc-flash-and-internal-arc-classification/).
6. **Protection and control:** relay functions, CT and VT ratios and classes, interlocking, auxiliary supply voltage, SCADA protocol.
7. **Installation conditions:** indoor or outdoor, altitude, ambient temperature, humidity, pollution, seismic zone and IP rating.
8. **Documentation and tests:** type test reports for the design, routine tests per panel, and whether you want to witness the factory acceptance test.

The [Kenya 33 kV/11 kV urban distribution substation application example](https://www.toppower-asia.com/projects/kenya-33kv-11kv-substation/) shows how an MV line-up fits into a representative substation design.

## Frequently asked questions

### What voltage is considered medium voltage switchgear?

Under IEC 62271-200, metal-enclosed switchgear from above 1 kV up to and including 52 kV is the MV range. In practice, most MV switchgear is rated 12 kV, 24 kV or 36 kV (or 15 kV, 27 kV and 38 kV in North America).

### What is the difference between 12 kV, 24 kV and 36 kV switchgear?

The figure is the rated (maximum) voltage. 12 kV switchgear serves 10–11 kV networks, 24 kV serves 20–22 kV networks and 36 kV serves 33 kV networks. Higher ratings need larger clearances or better insulation, so panels become wider and deeper, and insulation levels rise.

### Is KYN28 switchgear metal-clad?

KYN28 is an armoured, withdrawable, air-insulated design with separate compartments for the breaker, busbars, cables and low-voltage equipment. It is commonly described as metal-clad. For IEC projects, specify the LSC category, partition class and IAC rather than relying on the label.

### What is air-insulated switchgear?

Air-insulated switchgear uses atmospheric air as the main insulation between live parts and earth. It is simple, easily maintained and free of fluorinated gases, but it is larger than gas-insulated equipment and more sensitive to humidity, dust and altitude.

### How long does MV switchgear take to manufacture?

It depends on the design, quantity and the availability of breakers, relays and instrument transformers. Ask suppliers for a lead time based on your final single-line diagram, and allow time for drawing approval and factory testing.

If you are planning a primary or secondary substation, [send us your single-line diagram and network data](https://www.toppower-asia.com/contact/) and our engineering team will return a technical proposal with the recommended MV switchgear arrangement and ratings.