# Grounding (earthing) transformers and zigzag connections

Published 2026-10-13 by Toppower Asia Engineering Team · https://www.toppower-asia.com/blog/grounding-transformer-zigzag/

A grounding transformer (earthing transformer) gives a delta-connected or unearthed three-phase system a neutral point that can carry earth fault current. It presents a high impedance to normal balanced voltages but a low impedance to zero-sequence current, so faults can be detected, cleared and limited. Most are zigzag (ZN) or wye-delta (YNd) units, often combined with a neutral earthing resistor.

## Key takeaways

- A delta winding has no neutral. Without one, an earth fault draws almost no current, protection cannot see it, and healthy phases can rise towards line voltage.
- A zigzag transformer is the most common earthing transformer: each core limb carries two half-windings from different phases, so zero-sequence fluxes cancel and only leakage impedance remains.
- Grounding transformer sizing is based on the earth fault current and its duration, not on continuous kVA. A 10-second rated unit is much smaller than a continuously rated transformer of the same short-time kVA.
- The earthing transformer's zero-sequence impedance, plus any resistor, sets the fault current. Specify it together with the protection scheme.

## What is a grounding transformer and why is it needed?

Earth faults are the most frequent fault type on overhead lines and cable networks. To clear them quickly, the system needs a path for fault current back to the source, and that path runs through an earthed neutral. On a star (wye) winding the neutral is available; on a delta winding it is not.

Delta windings are common at medium voltage. Many distribution networks are fed from a YNd main transformer with the delta on the MV side, and many renewable plants use step-up transformers with a delta MV winding. The [delta-wye transformer connections guide](https://www.toppower-asia.com/blog/delta-wye-transformer-connections/) explains why designers choose delta: it traps third-harmonic currents and isolates zero-sequence networks on either side of the transformer.

The cost of that choice is an unearthed MV system. On an unearthed system, the first earth fault causes only a small capacitive current. That sounds harmless, but it brings three problems:

- **Protection cannot detect the fault reliably**, so it can remain on the system for hours until a second fault on another phase turns it into a phase-to-phase fault.
- **The healthy phases rise towards line-to-line voltage**, stressing insulation, surge arresters and cable terminations.
- **Intermittent arcing faults can cause transient overvoltages** well above normal, which damage equipment elsewhere on the network.

An earthing transformer solves this by creating an artificial neutral. Its neutral terminal can be connected to earth solidly, through a resistor or through a reactor, and the system then behaves like an earthed system for fault purposes.

## How does a zigzag transformer work?

A zigzag (interconnected star) winding splits each phase into two equal half-windings placed on different core limbs. On each limb, one half-winding belongs to one phase and the other half-winding belongs to the next phase, connected in the opposite sense. The three outer ends connect to the system phases, and the three inner ends join to form the neutral.

Under balanced conditions, the two half-windings on each limb carry voltages from different phases, so a normal magnetising flux flows and the unit draws only a small magnetising current. It behaves like an unloaded transformer.

During an earth fault, a zero-sequence current flows into the neutral and divides equally between the three phases, one third in each. Because zero-sequence currents in all phases are in phase, the two half-windings on each limb carry equal currents in opposite directions. Their ampere-turns cancel, the core sees almost no net flux, and the only impedance left is the leakage impedance between the half-windings. That low zero-sequence impedance is exactly what an earthing transformer needs.

Two details matter for design. Each half-winding sees only 1/√3 of the phase-to-neutral voltage, so a zigzag winding needs about 15% more turns than a star winding for the same voltage. And a zigzag winding can share the core with a secondary winding, as in a ZNyn11 unit, which provides both the earthing point and a low-voltage auxiliary supply for the substation.

## Zigzag or wye-delta: which earthing transformer connection should you use?

Both connections do the same job. The choice depends on cost, auxiliary supply needs and the supplier's standard designs.

| Feature | Zigzag (ZN or ZNyn) | Wye-delta (YNd) |
|---|---|---|
| Windings | One zigzag winding, optional LV secondary | Star primary plus a closed delta winding |
| Zero-sequence path | Cancelling half-windings on each limb | Current circulates in the delta |
| Size for the same duty | Usually smaller and lighter | Usually larger, two full windings |
| Auxiliary LV supply | Possible with an added yn winding | Possible by loading the delta or adding a winding |
| Typical use | Purpose-built earthing transformer on MV buses | Where a standard star-delta design or an existing unit is reused |
| Standard reference | IEC 60076-6 (earthing transformers), IEEE C57.32 | Same |

A standard Dyn or YNd distribution transformer can sometimes be used, but it is designed for continuous load, not for a short, heavy zero-sequence current. Check its zero-sequence impedance and thermal capability before reusing one.

## How does a grounding transformer work with a neutral earthing resistor?

The earthing transformer creates the neutral; what you connect to it decides the earthing method. The table below compares the common options.

| Neutral grounding method | Fault current | Main benefit | Main drawback |
|---|---|---|---|
| Solid earthing | High, close to three-phase fault level | Low overvoltage, simple protection | High fault damage and touch voltage |
| Low-resistance earthing | Limited, typically hundreds of amperes | Limits damage while allowing fast, selective tripping | Resistor and transformer must be rated for the fault duration |
| High-resistance earthing | Very low, a few amperes | Allows continued operation with alarm on first fault | Resistor current must exceed the system's capacitive charging current |
| Reactance or resonant earthing | Low, tuned to capacitance in resonant schemes | Arc self-extinction on overhead lines | More complex protection and tuning |

IEEE practice treats a system as effectively grounded when the ratio of zero-sequence reactance to positive-sequence reactance (X0/X1) is not more than 3 and the ratio R0/X1 is not more than 1. Effective grounding keeps overvoltages on healthy phases low enough to use lower-rated surge arresters. Low- and high-resistance earthing are not effectively grounded, so arrester ratings must be chosen for the higher temporary overvoltage. IEEE 142 gives detailed guidance on choosing a method.

## How do you approach grounding transformer sizing?

Grounding transformer sizing is about the earth fault current and how long it flows, not about normal load. A typical sequence:

1. **Decide the earthing method and target fault current.** For low-resistance earthing, the limit is usually chosen so that earth fault relays operate reliably and cable screens can carry the current.
2. **Set the fault duration.** This is the maximum time the fault can last, including backup protection. Short-time ratings such as 10 seconds or 1 minute are common for units protected by tripping relays. If the scheme only alarms, a continuous rating is needed.
3. **Calculate the short-time rating.** The usual expression is phase-to-neutral voltage multiplied by neutral current, for the stated time.
4. **Specify the zero-sequence impedance.** The fault current is set by the source impedance, the transformer's zero-sequence impedance and three times any neutral resistance. With a resistor, the resistor usually dominates.
5. **Add any continuous duty.** Include standing neutral current from unbalance and any auxiliary load on a secondary winding.
6. **Check insulation levels.** The neutral of a resistance-earthed unit rises in voltage during a fault, so the neutral bushing and insulation must be rated for it.

### Worked example (illustration only)

A 33 kV collector bus is to be resistance-earthed with the earth fault current limited to 400 A for 10 seconds.

- Phase-to-neutral voltage: 33 kV / √3 ≈ 19.05 kV.
- Short-time rating: 19.05 kV × 400 A ≈ 7,620 kVA for 10 seconds.
- Current in each zigzag phase: 400 A / 3 ≈ 133 A.
- Neutral resistor, ignoring transformer and source impedance: 19,050 V / 400 A ≈ 47.6 Ω, rated 400 A for 10 seconds.

The transformer's own zero-sequence impedance reduces the fault current slightly, so the resistor value is normally fine-tuned once the transformer impedance is known. Because the unit only carries this current for 10 seconds, it is physically far smaller than a 7,620 kVA continuously rated transformer.

## Where should a grounding transformer be connected and protected?

An earthing transformer is usually connected to the MV bus through its own circuit breaker or switch-fuse, or directly to the delta-side terminals of the main transformer so it lies within that transformer's protection zone. On renewable plants, it is common to place one on each collector bus section, so every section remains earthed even if a bus coupler opens. Integrated [oil-immersed step-up substations for solar and wind](https://www.toppower-asia.com/products/transformer-substation/oil-immersed-step-up-substation-for-solar-wind/) and a representative [33 kV wind farm substation application example](https://www.toppower-asia.com/projects/chile-33kv-wind-farm-substation/) show where this equipment sits.

Points to cover in the protection design:

- **Earth fault protection** with a CT on the neutral connection, set to grade with feeder earth fault relays.
- **Overcurrent protection** on the phase connections for internal faults in the earthing transformer itself.
- **Interlocking or alarms** so the system is never run unearthed by mistake. If the earthing transformer trips, the network loses its earth reference.
- **Thermal protection** of the neutral resistor if the fault duration could exceed its rating.

## What should a grounding transformer specification include?

State the system voltage and Um, frequency, connection (ZN, ZNyn11 or YNd), zero-sequence impedance per phase or target fault current, neutral current and duration, any continuous neutral current, any secondary winding rating and voltage, insulation levels including the neutral, the neutral resistor data if supplied together, cooling, and the standard (IEC 60076-6 or IEEE C57.32). The [transformer RFQ checklist](https://www.toppower-asia.com/blog/transformer-rfq-checklist/) covers the general items such as losses, site conditions and tests.

## Frequently asked questions

### Is a grounding transformer the same as an earthing transformer?

Yes. "Grounding" is the North American term and "earthing" the IEC and British term. Both describe a transformer whose main job is to provide a neutral connection to earth on a system that does not otherwise have one.

### Can a zigzag transformer supply load?

A plain zigzag earthing transformer does not supply load; it only carries magnetising current and fault current. A ZNyn unit adds a secondary winding that can supply substation auxiliaries, and its rating must cover both the continuous auxiliary load and the short-time earth fault duty.

### Why is grounding transformer sizing based on short-time rating?

Earth fault protection clears faults within seconds, so the transformer only carries high current for a short time. Its windings are sized for the heat produced in that time, which is far less than the continuous rating with the same kVA would need. Specify the current and duration clearly; a wrong duration is the most common sizing mistake.

### What happens if the earthing transformer is out of service?

The network loses its neutral reference and behaves as an unearthed system. Earth faults may go undetected and overvoltages on healthy phases rise. Protection schemes often trip or block the associated source in this case.

### Which standard covers earthing transformers?

IEC 60076-6 covers reactors and includes earthing transformers, and IEEE C57.32 covers neutral grounding devices including grounding transformers and resistors. General transformer requirements still come from IEC 60076-1 or IEEE C57.12.00; see [IEC 60076 vs IEEE C57 transformer standards](https://www.toppower-asia.com/blog/iec-60076-vs-ieee-c57-transformer-standards/).

Planning a resistance-earthed MV system or a renewable collector network? Send us your single-line diagram, fault levels and protection philosophy, and the Toppower Asia engineering team will propose an earthing transformer and resistor arrangement with a technical proposal. [Contact us](https://www.toppower-asia.com/contact/).